ABB AC500 PLC - Parameterization

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameterization
Firmware version Configuration
Firmware version > V2.0.0 The arrangement of the parameter data is per-
formed by Control Builder Plus/ Automation
Builder software.
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configu-
ration.
Module: Module slot address: Y = 1...10
Name Value Internal
value
Internal
value,
type
Default Min. Max. EDS
Slot/
Index
Module ID Internal 1205
1
)
Word 1205
0x04B5
0 65535 0x0Y01
Ignore
module
2
)
No
Yes
0
1
Byte No
0x00
not for
FBP
Parameter
length
Internal 4 Byte 4-CPU
4-FBP
0 255 0x0Y02
Check
supply
Off
on
0
1
Byte On
0x01
0 1 0x0Y03
Input
delay
20 ms
100 ms
0
1
Byte 20 ms
0x00
0 1 0x0Y04
Behaviour
of outputs
at com-
munica-
tion errors
Off
Last value
Substitute
value
0
1+(n*5)
2+(n*5),
n £ 2
Byte Off
0x00
0 2 0x0Y05
Substitute
value at
outputs
Bit 3 =
Output 3
Bit 0 =
Output 0
0...15 0...
0x0f
Byte 0
0x00
0 15 0x0Y06
1
) With CS31 and addresses smaller than 70 and FBP, the value is increased by 1
2
) Not with FBP
GSD file:
Ext_User_Prm_Data_Len =
Ext_User_Prm_Data_Const
(0) =
7
0x04, 0xb6, 0x04, \
0x01, 0x00, 0x00, 0x00;
Device Specifications
I/O Modules > Digital I/O Modules
2019/04/17 3ADR010121, 13, en_US 389