Without the Fast Counter With the Fast Counter (only
with AC500)
Counter input data (words) 0 4
Counter output data (words) 0 8
I/O Configuration
The module itself does not store configuration data. It receives its parameterization data from
the master device of the I/O bus (CPU or bus module) during power-up of the system.
Hence, replacing I/O modules is possible without any re-parameterization via software.
If the external power supply voltage via UP/ZP terminals fails, the I/O module
loses its configuration data. The whole station has to be switched off and on
again to re-configure the module.
Parameterization
Firmware version Configuration
Firmware version > V2.0.0 The arrangement of the parameter data is per-
formed by Control Builder Plus/ Automation
Builder software.
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configu-
ration.
Module: Module slot address: Y = 1...10
No. Name Value Internal
value
Internal
value,
type
Default Min. Max. EDS
Slot/
Index
1 Module
ID
Internal 1000
1
)
Word 1000
0x03E8
0 65535 0x0Y01
2 Ignore
module
2
)
No
Yes
0
1
Byte No
0x00
Not for
FBP
3 Param-
eter
length
Internal 3-CPU
2-FBP
Byte 3
2
0 255 0x0Y02
4 Check
supply
Off
On
0
1
Byte On
0x01
0 1 0x0Y03
I/O Modules > Digital I/O Modules
2019/04/17 3ADR010121, 13, en_US 347