1.3.1.1 Technical Data (Overview)
CM574-
RCOM
CM574-
RS
CM579
-
ETHC
AT
CM582-DP
CM592-DP
CM598-CN
CM588-CN
CM589-
PNIO(-4)
CM579-PNIO
CM597-ETH
Field bus RCOM/
RCOM+
Serial
(ASCII/
Modbus)
EtherC
AT
PROFIBUS
DP
CANopen PROFINET 2 x Ethernet
Transmission
rate
2.4 kBit/s
to 19.2
kBit/s
9.6 kBit/s
to 187.5
kBit/s
10
MBit/s
or
100
MBit/s
9.6 kBit/s to
12 MBit/s
10 kBit/s to 1
MBit/s
100 MBit/s 10 MBit/s or
100 MBit/s
Field bus con-
nector
MC 0.5/9-G-2.5, 9-pin,
male
2 x
RJ45
D-sub, 9-
pin, female,
bended
COMBICON
2x 5-pin,
bended
2 x RJ45
Processor PowerPC Hilscher netX100
Ambient tem-
perature
0 °C...60 °C (standard version)
-30 °C ... +70 °C (XC version only)
Communica-
tion Module
interface
Dual-port memory, 8
kByte
Dual-port memory, 16 kByte
Current con-
sumption
from 24 V DC
power supply
at the ter-
minal base of
the CPU
Typ. 80 mA Typ. 85
mA
Typ. 65 mA Typ. 85 mA
Internal RAM
memory
256 kByte 128 kByte
External RAM
memory
- 8 MByte
External flash
memory
- 512
kByte
(firm-
ware) + 2
x 64
kByte
(user
data)
4
MByte
or
8
MByte
8 MByte 4
MByte
or
8
MByte
8 MByte
Status display PWR
RDY
RUN
STA
ERR
PWR
RDY
RUN
STA1
STA2
2x
LINK
2x ACT
PWR
RDY
RUN
STA
ERR
PWR
RDY
RUN
CAN-RUN
CAN-ERR
PWR
RDY
RUN
STA1
STA2
2x LINK
2x ACT
PWR
RDY
RUN
STA
ERR
2x LINK
2x ACT
Weight 150 g 170 g 150 g 170 g
Device Specifications
Communication Modules (AC500 Standard) > Overview
2019/04/173ADR010121, 13, en_US94

Table of Contents