Channel Parameters for the Analog Outputs (2x)
Name Value Internal value Internal value,
type
Default
Output 0,
Channel configu-
ration
Operation modes
of analog outputs
Operation modes
of analog outputs
BYTE 0
Output 0, Check
channel
Channel moni-
toring
Channel moni-
toring
BYTE 0
Output 0, Substi-
tute value
Substitute value Substitute value WORD 0
Output 1,
Channel configu-
ration
Operation modes
of analog outputs
Operation modes
of analog outputs
BYTE 0
Output 1, Check
channel
Channel moni-
toring
Channel moni-
toring
BYTE 0
Output 1, Substi-
tute value
Substitute value Substitute value WORD 0
Table 114: Channel Configuration - Operating Modes of the Analog Outputs
Internal value Operating Modes (individually configu-
rable)
0 (default) Not used
128 -10 V...+10 V
129 0...20 mA
130 4...20 mA
Table 115: Channel Monitoring
Internal value Check channel
0 Plausib(ility), cut wire, short circuit
3 None
Table 116: Substitute Value
Intended Behavior of Output
Channel when the Control
System Stops
Required Setting of the
Module Parameter
"Behavior of Outputs in
Case of a Communication
Error"
Required Setting of the
Channel Parameter "Substi-
tute value"
Output OFF Off 0
Last value infinite Last value 0
Last value for 5 s and then
turn off
Last value 5 sec 0
Last value for 10 s and then
turn off
Last value 10 sec 0
Substitute value infinite Substitute value Depending on configuration
Device Specifications
Communication Interface Modules (S500) > CANopen
2019/04/173ADR010121, 13, en_US724