ABB AC500 PLC - 1.2.2.2.6 Technical Data

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Button Description
RESET If pressed during power-on: Enter serial download of firmware. This is
signalized by blinking of the RUN LED with a frequency of 1 Hz. If
pressed during normal operation: reserved for future implementation.
Fn If pressed during power-on: Bootproject will not be loaded. This is sig-
nalized by blinking of the RUN LED with a frequency of 1 Hz. If pressed
during normal operation: reserved for future implementation.
RUN/STOP Switches the processor module from RUN to STOP mode.
The AC500 processor module can display various errors according to the error classes. The
reaction of the Processor Module is different for each type of error. See System Technology
LED display.
1.2.2.2.6 Technical Data
The System Data of AC500 and S500
Ä
Chapter 2.6.1 “System Data AC500” on page 1248 are
valid for standard version.
The System Data of AC500-XC
Ä
Chapter 2.7.1 “System Data AC500-XC” on page 1309 are
valid for the XC version.
Only additional details are therefore documented below.
Parameter Value
Connection of the supply voltage 24 VDC at the
removable terminal block of the processor
module
at a removable 5-pin terminal block with
spring connection
Current consumption from 24 VDC 0.4 A
Inrush current at 24 VDC 1 A²s *)
Max. power dissipation within the module 15 W
Slots for communication modules 2
Processing module's interfaces I/O bus, COM1, COM2
Processing module's network interfaces ETH1 and ETH2 for Ethernet-based system
communication
ETH3.1 and ETH3.2 for Ethernet-based
fieldbuses with switch functionality
ETH4.1 and ETH4.2 for Ethernet-based
fieldbuses with switch functionality
Connection system
see System Assembly chapter
Ä
Chapter
2.6.4 “Connection and Wiring” on page 1272
Weight 1070 g
Mounting position horizontal or vertical with derating (50 %
output load, reduction of temperature to 40
°C)
*1) The melting integral of the processor module depends on the processor module's integrated
power supply, and the number and type of communication modules and I/O modules connected
to the I/O bus.
General data of
the Processor
Modules
Device Specifications
Processor Modules > AC500 (Standard)
2019/04/17 3ADR010121, 13, en_US 89