ABB AC500 PLC - Connection of Active-type Analog Sensors (Voltage) with Electrically Isolated Power Supply

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connection of Active-type Analog Sensors (Voltage) with Electrically Isolated Power Supply
UP
ZP
1.0
I0-
1.1
I0B
1.8
UP
1.9
ZP
PTC
2.0
I0+
2.1
I0A
2.8
UP
2.9
ZP
-50 ... +50 mV
-500 ... +500 mV
-1 ... +1 V
-5 ... +5 V
-10 ... +10 V
-50 ... +50 mV
0 ... +5 V
0 ... +10 V
+
-
U
IN
Fig. 42: Connection example
The measuring ranges can be configured
Ä
Chapter 1.5.2.2.2.6 “Parameterization”
on page 489:
Voltage -50 mV...+50 mV 1 channel used
Voltage -500 mV...+500 mV 1 channel used
Voltage -1 V...+1 V 1 channel used
Voltage -5 V...+5 V 1 channel used
Voltage -10 V...+10 V 1 channel used
Voltage 0 V...+5 V 1 channel used
Voltage 0 V...+10 V 1 channel used
Fig. 43: Connection example
The measuring range can be configured
Ä
Chapter 1.5.2.2.2.6 “Parameterization” on page 489:
Voltage Common mode voltage 1 channel used
Standard
Ranges
Common Mode
Range (+/-20 V)
Device Specifications
I/O Modules > Analog I/O Modules
2019/04/173ADR010121, 13, en_US476