Parameter Value
Bandwidth low min. 3 dB/< 0.1 Hz min. 3 dB/< 0.1 Hz or DC
(selectable)
Dynamic range (SFDR) > 100 dB
SINAD (300 Hz/1 kHz sine, 50 k
SPS)
0 dB from full scale < -90 dB < -95 dB
-20 dB from full scale < -75 dB < -80 dB
-40 dB from full scale < -55 dB < -60 dB
Input range +2 V...+18 V -10 V...+10 V
Measurement range +/-6 V (DC coupled) -10 V...+10 V
Input DC bias range, common mode
range
+8 V...+12 V +/-1 V
Current source per channel Typ. 4.2 mA (+/- 7 % over
temperature)
-
Input resistance AI- to M Typ. 27 Ohm (PTC)
Channel input impedance (AI+/AI-)
< 1 kHz > 1 MOhm > 2 MOhm
5 kHz > 100 kOhm > 40 kOhm
10 kHz > 60 kOhm > 25 kOhm
20 kHz > 40 kOhm > 8 kOhm
Error detection Short circuit, open wire -
Max. cable length, shielded
(depending on sensor)
100 m
1.6.2.2.7 Ordering Data
Part No. Description Product Life Cycle Phase *)
1SAP260400R0001 Function module FM502-CMS Active
1SAP460400R0001 Function module FM502-CMS-XC,
XC version
Active
*) For planning and commissioning of new installations use modules in Active
status only.
Device Specifications
Function Modules > S500
2019/04/17 3ADR010121, 13, en_US 697