Parameter Value
Undefined signal +5 V ... +15 V
Signal 1 +15 V...+30 V
Input current per channel
Input voltage +24 V Typ. 7 mA
Input voltage +5 V Typ. 1.4 mA
Input voltage +15 V Typ. 3.7 mA
Input voltage +30 V < 9 mA
Input resistance Ca. 3.5 kW
Technical Data of the Analog Outputs
Parameter Value
Number of channels per module 2
Distribution of channels into groups 1 group for 2 channels
Connection of the channels AO0+...AO1+ Terminals 2.5 ... 2.6
Reference potential for AO0+ to AO1+ Terminal 2.7 (AO-) for voltage output
Terminal 2.9, 3.9 and 4.9 for current output
Output type
Unipolar Current
Bipolar Voltage
Electrical isolation Against PROFIBUS
Configurability -10 V...+10 V, 0 mA...20 mA, 4 mA...20 mA
(each output can be configured individually)
Output resistance (load), as current output 0...500 W
Output loadability, as voltage output ±10 mA max.
Indication of the output signals 1 LED per channel (brightness depends on the
value of the analog signal)
Resolution 12 bits (+ sign)
Conversion error of the analog values
caused by non-linearity, adjustment error at
factory and resolution within the normal
range
Typ. 0.5 %, max. 1 %
Relationship between input signal and hex
code
Table Output Ranges Voltage and Current
Unused outputs Are configured as "unused" (default value) and
can be left open-circuited
Technical Data of the Fast Counter
Parameter Value
Used inputs Terminal 3.0 (DI0), 3.1 (DI1)
Used outputs Terminal 4.0 (DO0)
Device Specifications
Communication Interface Modules (S500) > PROFIBUS
2019/04/17 3ADR010121, 13, en_US 979