ABB AC500 PLC - 1.6.2.2.3 Diagnosis

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1.6.2.2.3 Diagnosis
Table 97: Module Error FM502-CMS
E1...E4 d1 d2 d3 d4 Identi-
fier
000...06
3
AC500
display
<-- Display in
Class Comp Dev Mod Ch Err PS501
PLC
browser
Byte 6
Bit 6...7
- Byte 3 Byte 4 Byte 5 Byte 6
Bit 0...5
FBP
diag-
nosis
block
Class Inter-
face
Device Module Channel Error
identi-
fier
Error
mes-
sage
Online
number
Remedy
1
)
2
)
3
)
4
)
3 5 255 29 31 3 Timeout
in the I/O
module
1845452
19
Replace
I/O
module
3 5 255 29 31 11 Process
voltage
too low
1845452
27
Replace
I/O
module
4 5 255 29 31 13 FW
update
failed
1845452
29
Retry
FW
update
3 5 255 29 31 18 5 V
sensor
supply
too low
1845452
34
Check
wiring &
sensor
power,
Replace
I/O
module
3 5 255 29 31 19 Checksu
m error
in the I/O
module
1845452
35
Replace
I/O
module
3 5 255 29 31 36 Internal
data
exchang
e failure
1845452
52
Replace
I/O
module
3 5 255 29 31 43 Internal
error in
the
module
1845452
59
Replace
I/O
module
4 5 255 29 31 52 Produc-
tion data
missing
1845452
68
Call sup-
port
Device Specifications
Function Modules > S500
2019/04/17 3ADR010121, 13, en_US 685