3
)
With "Module" the following allocation applies depending on the master:
Module error: I/O bus or FBP: 31 = module itself; COM1/COM2: 1...10 =
expansion 1...10
Channel error: I/O bus or FBP = module type (2 = DO); COM1/COM2: 1...10
= expansion 1...10
4
)
In case of module errors, with channel "31 = module itself" is output.
State LEDs
During the power ON procedure, the module initializes automatically. All LEDs (except the
channel LEDs) are ON during this time.
LED State Color LED = OFF LED = ON LED flashes
Inputs
I0...I7
Digital input Yellow Input = OFF Input = ON --
Outputs
R0...R3
(relays)
Digital output Yellow Relay output
= OFF
Relay output =
ON
--
UP Process
supply
voltage
24 VDC via
terminal
Green Process
supply
voltage is
missing
Process
supply voltage
OK
--
CH-ERR2 Channel
error, error
messages in
groups (dig-
ital inputs/
outputs com-
bined into the
groups 2 and
3)
Red No error or
process
supply
voltage is
missing
Severe error
within the cor-
responding
group
Error on one
channel of the
corresponding
group
CH-ERR3 Red
CH-ERR *) Module Error Red -- Internal error --
*) All of the LEDs CH-ERR2 to CH-ERR3 light up together
Technical Data
The System Data of AC500 and S500
Ä
Chapter 2.6.1 “System Data AC500” on page 1248 are
valid for standard version.
The System Data of AC500-XC
Ä
Chapter 2.7.1 “System Data AC500-XC” on page 1309 are
valid for the XC version.
Only additional details are therefore documented below.
Parameter Value
Process supply voltage UP
Connections Terminals 1.8, 2.8, 3.8 and 4.8 for
+24 VDC (UP) as well as 1.9, 2.9,
3.9 and 4.9 for 0 VDC (ZP)
I/O Modules > Digital I/O Modules