Range Digital value
Decimal Hex.
Measured value too low -501
:
-600
FE0B
:
FDA8
Underflow -32768 8000
Resistor Input Range
Range Resistor [W]
Overflow > 55000
Measured value too high 55000
:
50001
Normal range 50000
:
2
1
0
The represented resolution corresponds to 16 bits.
Range Digital value
Decimal Hex.
Overflow 32767 7FFF
Measured value too high 30413
:
27649
76CD
:
6C01
Normal range 27648
:
1
1
0
6C00
:
0001
0001
0000
Thermocouple Input Ranges
Range Typ J
-210 ... +1200
°C
Typ K
-270 ... +1372
°C
Typ N
-270 ... +1300
°C
Typ S
-50 ... +1768
°C
Typ T
-270 ... +400
°C
Overflow > 1200.0 °C > 1372.0 °C > 1300.0 °C > 1768.0 °C > 400.0 °C
Normal range 1768.0 °C
1372.0 °C :
I/O Modules > Analog I/O Modules
2019/04/173ADR010121, 13, en_US500