Parameter Value
Switching Frequencies
With inductive loads Max. 0.5 Hz
With lamp loads Max. 11 Hz at max. 5 W
Short-circuit-proof / Overload-proof No
Overload message No
Output current limitation No
Resistance to feedback against 24
VDC
No
Connection of 2 outputs in parallel Not possible
Max. cable length
Shielded 500 m
Unshielded 150 m
Ordering Data
Part No. Description Product Life Cycle Phase *)
1TNE 968 902 R2201 DO561, digital output module, 8 DO,
transistor output
Active
1TNE 968 901 R3102 Terminal block TA563-11, 11 pins,
screw front, cable side, 6 pieces per
unit
Active
1TNE 968 901 R3104 Terminal block TA564-11, 11 pins,
screw front, cable front, 6 pieces per
unit
Active
1TNE 968 901 R3106 Terminal block TA565-11, 11 pins,
spring front, cable front, 6 pieces per
unit
Active
*) For planning and commissioning of new installations use modules in Active
status only.
1.5.1.1.8 DO562 - Digital Output Module
● 16 digital outputs 24 VDC (O0 to O15) in 1 group
● Module-wise electrically isolated
I/O Modules > Digital I/O Modules
2019/04/173ADR010121, 13, en_US230