EasyManua.ls Logo

ABB AC500 PLC - 1.4.6.1 Technical Data; 1.4.6.2 Ordering Data

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1.4.6.1 Technical Data
The System Data of AC500 and S500
Ä
Chapter 2.6.1 “System Data AC500” on page 1248 are
valid for standard version.
The System Data of AC500-XC
Ä
Chapter 2.7.1 “System Data AC500-XC” on page 1309 are
valid for the XC version.
Only additional details are therefore documented below.
Parameter Value
Number of channels per module 32
Distribution of the channels into groups 4 groups of 8 channels each (1.0...1.7,
2.0...2.7, 3.0...3.7, 4.0...4.7), the allocation of
the channels is given by the inserted I/O
module
Rated voltage 230 VAC
Max. permitted total current 10 A (between the terminals 1.8...4.8 and
1.9...4.9)
Earthing Direct connection to the earthed DIN rail or via
the screws with wall mounting
Screw terminals Front terminal, conductor connection vertically
with respect to the printed circuit board
Spring terminals Front terminal, conductor connection vertically
with respect to the printed circuit board
Weight 200 g
Mounting position Horizontal or vertical
1.4.6.2 Ordering Data
Part No. Description Product Life Cycle Phase *)
1SAP 217 200
R0001
TU531, terminal unit, 230 VAC, relays,
screw terminals
Active
1SAP 217 000
R0001
TU532, terminal unit, 230 VAC, relays,
spring terminals
Active
1SAP 417 000
R0001
TU532-XC, terminal unit, 230 VAC,
relays, spring terminals, XC version
Active
1SAP 215 100
R0001
TU532-H, terminal unit, hot swap,
230 VAC, relays, spring terminals
Active
1SAP 415 100
R0001
TU532-H-XC, terminal unit, hot swap,
230 VAC, relays, spring terminals, XC
version
Active
*) For planning and commissioning of new installations use modules in Active
status only.