ABB AC500 PLC - 1.7.1.3.10 Technical Data

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
LED Color OFF ON Flashing
CN-ERR Red No system error CANopen Bus is
OFF
Flashing: Config-
uration error
Single flash: error
counter overflow
due to too many
error frames
Double flash: A
node-guard or a
heartbeat event
occurred
Flickering: Auto-
detect is active
S-ERR Red No error Internal error --
I/O bus Green No decentralized
I/O modules con-
nected or com-
munication error
Decentralized I/O
modules con-
nected and
operational
---
LED Color OFF ON Flashing
DC0 to DC7 Yellow Input/output is OFF Input/output is ON --
DI8 to DI15 Yellow Input is OFF Input is ON (the input
voltage is even dis-
played if the supply
voltage is OFF)
--
DO8 to DO15 Yellow Output is OFF Output is ON --
UP Green Process supply
voltage missing
Process supply
voltage OK and initi-
alization finished
--
UP3 Green Process supply
voltage missing
Process supply
voltage OK
--
CH-ERR1 to
CH-ERR3
Red No error or process
supply voltage
missing
Internal error Error on one channel
of the corresponding
group
1.7.1.3.10 Technical Data
The System Data of AC500 and S500
Ä
Chapter 2.6.1 “System Data AC500” on page 1248 are
valid for standard version.
The System Data of AC500-XC
Ä
Chapter 2.7.1 “System Data AC500-XC” on page 1309 are
valid for the XC version.
Only additional details are therefore documented below.
Multiple overloads
No effects of multiple overloads on isolated multi-channel modules occur, as
every channel is protected individually by an internal smart high-side switch.
States of the 29
Process LEDs
Device Specifications
Communication Interface Modules (S500) > CANopen
2019/04/17 3ADR010121, 13, en_US 755