EasyManua.ls Logo

ABB AC500 PLC - Internal Data Exchange; I;O Configuration; Parameterization

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Internal Data Exchange
Without the Fast Counter With the Fast Counter (only
with AC500)
Digital inputs (bytes) 2 4
Digital outputs (bytes) 2 4
Counter input data (words) 0 4
Counter output data (words) 0 8
I/O Configuration
The module itself does not store configuration data. It receives its parameterization data from
the master device of the I/O bus (CPU or bus module) during power-up of the system.
Hence, replacing I/O modules is possible without any re-parameterization via software.
If the external power supply voltage via UP/ZP terminals fails, the I/O module
loses its configuration data. The whole station has to be switched off and on
again to re-configure the module.
Parameterization
Firmware version Configuration
Firmware version > V2.0.0 The arrangement of the parameter data is per-
formed by Control Builder Plus/ Automation
Builder software.
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configu-
ration.
Module: Module slot address: Y = 1...10
Name Value Internal
value
Internal
value,
type
Default Min. Max. EDS Slot/
Index
Module ID Internal 1220
1
)
Word 1220
0x04C4
0 65535 0x0Y01
Ignore
module
2
)
No
Yes
0
1
Byte No
0x00
Not for
FBP
Parameter
length
Internal 7 Byte 7-CPU
6-FBP
0 255 0x0Y02
Check
supply
Off
On
0
1
Byte On
0x01
0 1 0x0Y03
Device Specifications
I/O Modules > Digital I/O Modules
2019/04/173ADR010121, 13, en_US302

Table of Contents

Related product manuals