Electromagnetic Compatibility
ESD with communication connectors In order to prevent operating malfunctions,
it is recommended, that the operating per-
sonnel discharge themselves prior to
touching communication connectors or
perform other suitable measures to reduce
effects of electrostatic discharges.
Immunity against the influence of radiated
(CW radiated):
According to IEC 61000-4-3, zone B, crite-
rion A
Test field strength 10 V/m
Immunity against transient interference vol-
tages (burst):
According to IEC 61000-4-4, zone B, crite-
rion B
Supply voltage units (DC) 2 kV
Supply voltage units (AC) 2 kV
Digital inputs/outputs (24 VDC) 1 kV
Digital inputs/outputs (120 VAC...2400
VAC)
2 kV
Analog inputs/outputs 1 kV
CS31 system bus 1 kV
Serial RS-485 interfaces (COM) 1 kV
Serial RS-232 interfaces (COM, not for
PM55x and PM56x)
1 kV
ARCNET 1 kV
FBP 1 kV
Ethernet 1 kV
I/O supply, DC-out 1 kV
Immunity against the influence of line-con-
ducted interferences (CW conducted):
According to IEC 61000-4-6, zone B, crite-
rion A
Test voltage 3 V zone B, 10 V is also met.
High energy surges According to IEC 61000-4-5, zone B, crite-
rion B
Power supply AC 2 kV CM / 1 kV DM ²)
Power supply DC 1 kV CM / 0.5 kV DM ²)
DC I/O supply, add. DC-supply-out 0.5 kV CM / 0.5 kV DM ²)
Buses, shielded 1 kV CM ²)
AC I/O unshielded 2 kV CM / 1 kV DM ²)
I/O analog, I/O DC unshielded 1 kV CM / 0.5 kV DM ²)
Radiation (radio disturbance) According to IEC 55011, group 1, class A
1
) High requirement for shipping classes are achieved with additional specific measures (see
specific documentation).
²) CM = Common Mode, DM = Differential Mode