Parameter Value
  Voltage 120 V (-15 %, +10 %)
Frequency 50/60 Hz (-6 %, +4 %)
230 VAC  
  Voltage 230 VAC (-15 %, +10 %)
Frequency 50/60 Hz (-6 %, +4 %)
120 VAC...240 VAC wide range supply  
  Voltage 120 V...240 V (-15 %, +10 %)
Frequency 50/60 Hz (-6 %, +4 %)
Allowed interruptions of power supply, according to EN 61131-2
  DC supply Interruption < 10 ms, time between 2 interrup-
tions > 1 s, PS2
  AC supply Interruption < 0.5 periods, time between 2
interruptions > 1 s
NOTICE!
Exceeding the maximum power supply voltage for process or supply voltages
could lead to unrecoverable damage of the system. The system could be
destroyed.
NOTICE!
Improper voltage level or frequency range which cause damage of AC inputs:
– AC voltage above 264 V
– Frenquency below 47 Hz or above 62.4 Hz
NOTICE!
Improper connection leads cause overtemperature on terminals.
PLC modules may be destroyed by using wrong cable type, wire size and cable
temperature classification.
Parameter Value
Temperature  
  Operating 0 °C...+60 °C: Horizontal mounting of modules.
0 °C...+40 °C: Vertical mounting of modules.
Output load reduced to 50 % per group.
  Storage -40 °C...+70 °C
  Transport -40 °C...+70 °C
Humidity Max. 95 %, without condensation
Air pressure  
  Operating > 800 hPa / < 2000 m
  Storage > 660 hPa / < 3500 m
Ingress protection IP20
 
System Assembly, Construction and Connection
AC500 (Standard) > System Data AC500
2019/04/17 3ADR010121, 13, en_US 1249