EasyManua.ls Logo

ABB AC500 PLC - Page 1279

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Pin Signal Interface Description
Terminal
block
removed
Terminal
block
inserted
4 Terminator N RS-485 Terminator N
5 RTS RS-232 Request to send
(output)
6 TxD RS-232 Transmit data
(output)
7 SGND Signal Ground
8 RxD RS-232 Receive data
(input)
9 CTS RS-232 Clear to send
(input)
If the RS-485 bus is used, each interconnected bus line (each bus segment) must be electrically
terminated. The following is necessary:
2 resistors of 120 Ω each at both line ends (to avoid signal reflections)
Pull-up resistor at RxD/TxD-P and a pull-down resistor at RxD/TxD-N. These 2 resistors
care for a defined high level on the bus, while there is no data exchange.
It is useful, to activate both the pull-up and the pull-down resistors, which only are necessary
once on every bus line, at the bus master. For this reason, these two resistors are already inte-
grated within the COM1 interface of the AC500 terminal bases. They can be activated by con-
necting the terminals 1-2 and 3-4 of COM1.
The following drawing shows an RS-485 bus with the bus master at the line end.
1 Master at the bus line end, pull-up and pull-down activated, bus termination with 120 Ω
resistors
2 Slave within the bus line
3 Slave at the bus line end, bus termination with 120 Ω resistors
If the master is located within the bus line, it does not need a terminating resistor. The pull-up
and the pull-down resistors, however, must be activated (see the following drawing).
RS-485 bus
System Assembly, Construction and Connection
AC500 (Standard) > Connection and Wiring
2019/04/17 3ADR010121, 13, en_US 1279

Table of Contents

Related product manuals