For RS-422, no external line-terminating resistors have to connected. They are
already connected inside the module.
Table 188: Assignment of the terminals of removable connector X13 (CANopen interface)
Terminal Signal Description
1 TERM+ Internal line-terminating-resistor for CAN Bus. Bridging to
CAN HIGH terminal if bus termination is required
2 CAN+ Non-inverted CAN data terminal
3 CAN- Inverted CAN data terminal
4 TERM- Internal line-terminating-resistor for CAN Bus. Bridging to
CAN LOW terminal if bus termination is required
5 Not used Not used
6 Not used Not used
7 CAN_GND CAN ground terminal
8 Not used Not used
9 Not used Not used
WARNING!
Removal/Insertion under power
The devices are not designed for removal or insertion under power. Because of
unforeseeable consequences, it is not allowed to plug or unplug devices with
the power being ON.
Make sure that all voltage sources (supply and process voltage) are switched
off before you
connect or disconnect any signal or terminal block
remove, mount or replace a module.
Disconnecting any powered devices while energized in a hazardous location
could result in an electric arc, which could create a flammable ignition resulting
in fire or explosion.
Make sure that power is removed and that the area has been thoroughly
checked to ensure that flammable materials are not present prior to proceeding.
The devices must not be opened when in operation. The same applies to the
network interfaces.
NOTICE!
Risk of damaging the PLC modules!
Overvoltages and short circuits might damage the PLC modules.
Make sure that all voltage sources (supply and process voltage) are
switched off before you begin with operations at the system.
Never connect any voltages or signals to reserved terminals (marked with
---). Reserved terminals may carry internal voltages.
The module provide several diagnosis functions
Ä
Chapter 1.7.6.5.8 “Diagnosis” on page 1095.
Further information is provided in the System Technology chapter PROFINET.
Device Specifications
Communication Interface Modules (S500) > PROFINET
2019/04/173ADR010121, 13, en_US1088