Name Value Internal value Internal value,
type
Default
Input 3, Channel
configuration
see table
1
) see table
1
)
BYTE 0
Input 3, Check
channel
see table
2
) see table
2
)
BYTE 0
Table 121: Channel Configuration
1
)
Internal value Operating modes of the analog inputs, individually configu-
rable
0 (default) Not used
1 0...10 V
2 Digital input
3 0...20 mA
4 4...20 mA
5 -10 V...+10 V
8 2-wire Pt100 -50...+400 °C
9 3-wire Pt100 -50...+400 °C *)
10 0...10 V (voltage diff.) *)
11 -10 V...+10 V (voltage diff.) *)
14 2-wire Pt100 -50...+70 °C
15 3-wire Pt100 -50...+70 °C *)
16 2-wire Pt1000 -50...+400 °C
17 3-wire Pt1000 -50...+400 °C *)
18 2-wire Ni1000 -50...+150 °C
19 3-wire Ni1000 -50...+150 °C *)
*) In the operating modes with 3-wire configuration or with differ-
ential inputs, two adjacent analog inputs belong together (e.g. the
channels 0 and 1). In these cases, both channels are configured
in the desired operating mode. The lower address must be the
even address (channel 0). The next higher address must be the
odd address (channel 1). The converted analog value is available
at the higher address (channel 1).
Table 122: Channel Monitoring
2
)
Internal Value Check Channel
0 (default) Plausib(ility), cut wire, short circuit
3 Not used