2. While pressing down processor module pull it away from DIN rail.
NOTICE!
Risk of function faults!
Missing electrical contact by isolating screws or washers!
Use metal screws on the metal plate.
The metal plate must be included into the earthing concept of the plant.
Do NOT use isolating washers!
One TA566 Wall Mounting Accessory
Ä
Chapter 2.5.5.9 “ TA566 - Wall
Mounting Accessory” on page 1243 is needed per processor module.
1. Snap in the TA566 at the back side of the processor module.
Mounting a Pro-
cessor Module
on a Metal Plate
System Assembly, Construction and Connection
AC500-eCo > Mounting and Demounting
2019/04/17 3ADR010121, 13, en_US 1201