2 Parameters
2.2 List of parameters
SINAMICS G130/G150
100 List Manual (LH2), 04/2014, A5E03263479A
Dependency: Refer to: r0018, r0128, r0148, r0158, r0198
Note: Example:
The value 1010100 should be interpreted as V01.01.01.00.
Description: Displays the BIOS and EEPROM data version.
r0198[0]: BIOS version
r0198[1]: EEPROM data version EEPROM 0
r0198[2]: EEPROM data version EEPROM 1
Dependency: Refer to: r0018, r0128, r0148, r0158, r0197
Note: Example:
The value 1010100 should be interpreted as V01.01.01.00.
Description: Freely assignable name for a drive object.
In the commissioning software, this name cannot be entered using the expert list, but is specified in the configuration
assistant. The object name can be subsequently modified in the Project Navigator using standard Windows
resources.
Note: The parameter is not influenced by setting the factory setting.
Description: Displays the unique code number of the power unit.
Note: r0200 = p0201: No power unit found
For parallel circuit configurations, the parameter index is assigned to a power unit.
Description: Sets the actual code number from r0200 to acknowledge the power unit being used.
When commissioned for the first time, the code number is automatically transferred from r0200 into p0201.
r0198[0...2] BIOS/EEPROM data version / BIOS/EEPROM vers
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: - Calculated: - Access level: 4
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
p0199[0...24] Drive object name / DO name
All objects Can be changed: C1 Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 65535 0
r0200[0...n] Power unit code number actual / PU code no. act
B_INF, VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: PDS, p0120 Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
p0201[0...n] Power unit code number / PU code no
B_INF Can be changed: C2(2) Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: PDS, p0120 Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 65535 0