EasyManua.ls Logo

Siemens SINAMICS G150 - BI: Smart; Basic Line Module Operation; SLM;BLM Operation; Parking Pre-Setting; Parking Pre-Set; BI: Activate;De-Activate Power Unit Components; Pu_Comp Act;Deact

Siemens SINAMICS G150
1842 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
265
2 Parameters
2.2 List of parameters
Description: Setting to interconnect the ready signal for mixed operation of Smart Line Module (SLM) and Basic Line Module
(BLM).
In order that signal BO: r0873 is available at one of the infeeds, then BI: p0874 of the one infeed must be
interconnected to BO: r0863.0 of the other infeed.
Dependency: Refer to: r0863, r0873
Note: Mixed operation is not possible with the Active Line Module (ALM)!
Description: Pre-setting for the "Parking axis" and "Parking encoder" function.
Dependency: Refer to: p0480, p0897
Note: Re bit 00:
If there is at least one BICO interconnection for "Parking axis" or "Parking encoder", this default setting is taken into
consideration during power-up.
Description: Sets the signal source to activate/de-activate a power unit component.
Dependency: BI: p0895 = 0 signal
De-activate power unit components.
BI: p0895 = 1 signal
Activate power unit components
Refer to: p0125, r0126
Caution: It is not permissible to de-activate drive objects with safety functions enabled.
Notice: For Active Line Modules in the "Chassis" format, the Voltage Sensing Module (VSM, p0145) belonging to the power
unit is automatically activated/deactivated.
Note: The power unit is only de-activated when the pulses are suppressed.
For units connected in parallel, when one of the power units is de-activated, then the enable in p7001 is withdrawn.
p0874 BI: Smart/ Basic Line Module operation / SLM/BLM operation
B_INF Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 8732, 8832
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p0894 Parking pre-setting / Parking pre-set
ENC, VECTOR_G Can be changed: U, T Calculated: - Access level: 4
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Default with interconnection Park Do not park -
p0895[0...n] BI: Activate/de-activate power unit components / PU_comp act/deact
B_INF, VECTOR_G Can be changed: T Calculated: - Access level: 1
Data type: Unsigned32 / Binary Dyn. index: PDS, p0120 Func. diagram: -
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 1

Table of Contents

Other manuals for Siemens SINAMICS G150

Related product manuals