SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
265
2 Parameters
2.2 List of parameters
Description: Setting to interconnect the ready signal for mixed operation of Smart Line Module (SLM) and Basic Line Module
(BLM).
In order that signal BO: r0873 is available at one of the infeeds, then BI: p0874 of the one infeed must be
interconnected to BO: r0863.0 of the other infeed.
Dependency: Refer to: r0863, r0873
Note: Mixed operation is not possible with the Active Line Module (ALM)!
Description: Pre-setting for the "Parking axis" and "Parking encoder" function.
Dependency: Refer to: p0480, p0897
Note: Re bit 00:
If there is at least one BICO interconnection for "Parking axis" or "Parking encoder", this default setting is taken into
consideration during power-up.
Description: Sets the signal source to activate/de-activate a power unit component.
Dependency: BI: p0895 = 0 signal
De-activate power unit components.
BI: p0895 = 1 signal
Activate power unit components
Refer to: p0125, r0126
Caution: It is not permissible to de-activate drive objects with safety functions enabled.
Notice: For Active Line Modules in the "Chassis" format, the Voltage Sensing Module (VSM, p0145) belonging to the power
unit is automatically activated/deactivated.
Note: The power unit is only de-activated when the pulses are suppressed.
For units connected in parallel, when one of the power units is de-activated, then the enable in p7001 is withdrawn.
p0874 BI: Smart/ Basic Line Module operation / SLM/BLM operation
B_INF Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 8732, 8832
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p0894 Parking pre-setting / Parking pre-set
ENC, VECTOR_G Can be changed: U, T Calculated: - Access level: 4
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Default with interconnection Park Do not park -
p0895[0...n] BI: Activate/de-activate power unit components / PU_comp act/deact
B_INF, VECTOR_G Can be changed: T Calculated: - Access level: 1
Data type: Unsigned32 / Binary Dyn. index: PDS, p0120 Func. diagram: -
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 1