2 Parameters
2.2 List of parameters
Description: Displays the effective supplementary setpoint. The value shown is the additional setpoint after scaling.
Description: Displays the total effective setpoint.
The value indicates the sum of the effective main setpoint and supplementary setpoint.
Description: Sets the lowest possible motor speed.
This value is not undershot in operation.
Dependency: Refer to: p1106
Notice: The effective minimum speed is formed from p1080 and p1106.
Note: The parameter value applies for both motor directions.
In exceptional cases, the motor can operate below this value (e.g. when reversing).
Description: Sets the scaling for the maximum speed (p1082).
For a higher-level speed control, this scaling allows the maximum speed to be briefly exceeded.
Dependency: Refer to: p1082
Notice: Continuous operation above a scaling of 100 % is not permitted.
r1077 CO: Supplementary setpoint effective / Suppl setpoint eff
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 3030
P-Group: Setpoints Units group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
r1078 CO: Total setpoint effective / Total setpoint eff
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 3030
P-Group: Setpoints Units group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
p1080[0...n] Minimum speed / n_min
VECTOR_G Can be changed: C2(1), T Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 3050
P-Group: Setpoints Units group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.000 [rpm] 19500.000 [rpm] 0.000 [rpm]
p1081 Maximum speed scaling / n_max scal
VECTOR_G Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 3050, 3095
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
100.00 [%] 105.00 [%] 100.00 [%]