SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
897
2 Parameters
2.2 List of parameters
11: STOP B with delayed STO when the bus fails
12: STOP C with delayed STO when the bus fails
13: STOP D with delayed STO when the bus fails
14: STOP E with delayed STO when the bus fails
Dependency: Refer to: p9564, p9565
Notice: In the case of encoderless motion monitoring (p9506 = 1), only a value of 0 or 1 is permitted.
Note: In the extended sense, a bus failure should be seen here as a communication error in the control signals of the safety
functions (e.g. via PROFIsafe or TM54F).
SDI: Safe Direction (safe motion direction)
Description: Sets the velocity tolerance limit for the "SAM" function.
SAM is de-activated once the set velocity limit has been undershot.
Note: SAM: Safe Acceleration Monitor (safe acceleration monitoring)
SSM: Safe Speed Monitor (safety-relevant feedback signal from the velocity monitoring)
For p9568 = p9368 = 0, the following applies:
The value in p9546/p9346 (SSM) is applied as the velocity limit for SAM.
Description: Sets the velocity tolerance limit for the "SAM" function.
SAM is de-activated once the set velocity limit has been undershot.
Note: SAM: Safe Acceleration Monitor (safe acceleration monitoring)
SSM: Safe Speed Monitor (safety-relevant feedback signal from the velocity monitoring)
For p9568 = p9368 = 0, the following applies:
The value in p9546/p9346 (SSM) is applied as the velocity limit for SAM.
Description: Setting to select and de-select the acceptance test mode.
Value: 0: [00 hex] De-select the acceptance test mode
172: [AC hex] Select the acceptance test mode
Dependency: Refer to: p9558, r9571, p9601
Note: Acceptance test mode can only be selected if the safe motion monitoring functions are enabled.
p9568 SI Motion SAM velocity limit (Control Unit) / SI Mtn SAM v_limCU
VECTOR_G Can be changed: C2(95) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [mm/min] 1000.00 [mm/min] 0.00 [mm/min]
p9568 SI Motion SAM velocity limit (Control Unit) / SI Mtn SAM v_limCU
VECTOR_G (Safety
rot)
Can be changed: C2(95) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [rpm] 1000.00 [rpm] 0.00 [rpm]
p9570 SI Motion acceptance test mode (Control Unit) / SI Mtn Acc_mode
VECTOR_G Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0000 hex 00AC hex 0000 hex