2 Parameters
2.2 List of parameters
SINAMICS G130/G150
902 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the minimum current for encoderless actual value sensing referred to 1 A (i.e. 1 % = 10 mA).
- The value must be increased if C01711 has occurred with message value 1042.
- The value must be decreased if C01711 has occurred with message value 1041.
For synchronous motors, the following condition must be fulfilled:
|p0305 x p9783| >= p9588 x 1.2
Recommend.: If required, the correct value of the motor minimum current should be determined by making the appropriate
measurements.
Dependency: Refer to: r9785
Notice: If this percentage value is reduced excessively, then this can result in a safety message and an inaccurate actual
value.
Note: This parameter is only effective for encoderless actual value sensing (p9506/p9306 = 1, 3).
Description: Sets the acceleration limit to filter velocity fluctuations.
If this percentage value is increased, when accelerating, velocity peaks that do not reflect the real velocity
characteristic can occur.
If this value is decreased, and this dampens the velocity peaks when accelerating.
- The value must be increased if C01711 with message value 1043 has occurred.
- The value must be lowered if acceleration procedures have led to an excessive Safety actual velocity.
Recommend.: The setting of this parameter depends on the motor and closed-loop control, and must be newly determined for each
configuration.
To do this, a measurement should be performed while the actual value jumps, and the limit in r9785[0] must be set so
low using p9589, so that it is exceeded by the value in r9785[1] a maximum of four times per second. The actual
value correction filter intervenes at this instant in time. The step is no longer so drastic.
Dependency: Refer to: r9784
Note: This parameter is only effective for encoderless actual value sensing (p9506/p9306 = 1, 3).
For p9589 = maximum value, the filter is deactivated.
Diagnostics parameter p9784 must be used to correctly set this parameter.
Description: Displays the Safety Integrated version for the safe monitoring functions.
Index: [0] = Safety Version (major release)
[1] = Safety Version (minor release)
[2] = Safety Version (baselevel or patch)
[3] = Safety Version (hotfix)
p9588 SI Motion actual value sensing sensorless minimum current (CU) / ActVal sl I_min CU
VECTOR_G Can be changed: C2(95) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [%] 1000.00 [%] 10.00 [%]
p9589 SI Motion act. value sensing sensorless acceleration limit (CU) / ActVal sl a_lim CU
VECTOR_G Can be changed: C2(95) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
10.00 [%] 3300.00 [%] 100.00 [%]
r9590[0...3] SI Motion version safety motion monitoring (Control Unit) / SI Mtn version CU
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -