2 Parameters
2.2 List of parameters
SINAMICS G130/G150
680 List Manual (LH2), 04/2014, A5E03263479A
Dependency: Only effective for p4820 = 2 (staircase).
Units are dependent on p4810.
If p4810 = 1, 2, 4: The amplitude is referred to p2002 (reference current).
If p4810 = 3, 5: The amplitude is referred to p2000 (reference speed).
Description: Sets the offset (DC component) of the signal to be generated for the function generator.
Dependency: Units are dependent on p4810.
If p4810 = 1, 2, 4: The offset is referred to p2002 (reference current).
If p4810 = 3, 5: The offset is referred to p2000 (reference speed).
If p4810 = 2: In order to avoid the undesirable effects of play (backlash), the offset does not act on the current
setpoint, but instead on the speed setpoint.
Description: Sets the ramp-up time to the offset for the function generator.
Description: Sets the lower limit for the function generator.
Dependency: For p4810 = 2 the limit only applies to the current setpoint, but not the speed setpoint (offset).
Description: Sets the upper limit for the function generator.
Dependency: For p4810 = 2 the limit only applies to the current setpoint, but not the speed setpoint (offset).
p4826 Function generator offset / FG offset
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Trace and function generator Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
-1600.00 [%] 1600.00 [%] 0.00 [%]
p4827 Function generator ramp-up time to offset / FG ramp-up offset
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Trace and function generator Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
0.00 [ms] 100000.00 [ms] 32.00 [ms]
p4828 Function generator lower limit / FG lower limit
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Trace and function generator Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
-10000.00 [%] 0.00 [%] -100.00 [%]
p4829 Function generator upper limit / FG upper limit
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Trace and function generator Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
0.00 [%] 10000.00 [%] 100.00 [%]