SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
579
2 Parameters
2.2 List of parameters
Description: Sets the threshold value of the frequency difference to activate the closed-loop phase control for line-drive
synchronization.
The closed-loop phase control is activated (r3819.6 = 1), if the frequency difference is less that the threshold value.
Description: Displays the phase difference between the measured target phase and phase of the gating unit of the closed-loop
control for line-drive synchronization.
Description: Sets the phase setpoint for the line-drive synchronization.
Description: Sets the frequency limiting of the phase controller output for the line-drive synchronization.
Description: Displays the correction frequency for the line-drive synchronization.
p3806[0...n] Sync-line-drive frequency difference threshold value / Sync f_diff thresh
VECTOR_G Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 7020
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [Hz] 1.00 [Hz] 0.10 [Hz]
r3808 CO: Sync-line-drive phase difference / Sync phase diff
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 7020
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Scaling: p2005 Expert list: 1
Min Max Factory setting
- [°] - [°] - [°]
p3809[0...n] Sync-line-drive phase setpoint / Sync phase setp
VECTOR_G Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 7020
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-180.00 [°] 179.90 [°] 0.00 [°]
p3811[0...n] Sync-line-drive frequency limiting / Sync f_lim
VECTOR_G Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 7020
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [Hz] 1.00 [Hz] 0.20 [Hz]
r3812 CO: Sync-line-drive correction frequency / Sync f_corr
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 3080, 7020
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- [Hz] - [Hz] - [Hz]