SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
569
2 Parameters
2.2 List of parameters
Description: Sets the signal source for disabling DC-link voltage control on the motor side.
Description: Display and connector output for the unlimited setpoint of the active current controller of the DC link voltage control
on the motor side.
Description: Sets the signal source for power pre-control.
Dependency: Refer to: p3521
Note: Closed-loop control of the DC link voltage is improved by pre-controlling the power required for the other
components.
A scaled quantity is expected so that the various power reference values (r2004) of the drive objects must be taken
into account. The scaling factors are used to adapt the scaling (p3521).
Description: Sets the signal source for power pre-control.
Dependency: Refer to: p3521
Note: Closed-loop control of the DC link voltage is improved by pre-controlling the power required for the other modules.
A non-scaled quantity is expected so that the various power reference values (r2004) of the drive objects do not have
to be taken into account. The scaling factors are used to adapt the scaling (p3521).
p3513 BI: Voltage-controlled operation inhibit / U_ctrl op inhib
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 7960
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 1
r3517 CO: DC link controller active current setpoint / Vdc I_act set
VECTOR_G
(Tech_ctrl)
Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6220, 7960
P-Group: Closed-loop control Units group: 6_2 Unit selection: p0505
Not for motor type: - Scaling: p2002 Expert list: 1
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
p3519[0...3] CI: DC link pre-control power (scaled) / Vdc prectrl P scal
VECTOR_G
(Tech_ctrl)
Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Scaling: r2004 Expert list: 1
Min Max Factory setting
- - 0
p3520[0...3] CI: DC link pre-control power (not scaled) / Vdc pre-ctrl P
VECTOR_G
(Tech_ctrl)
Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / FloatingPoint32 Dyn. index: - Func. diagram: 7960
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0