3 Function diagrams
3.5 PROFIdrive
SINAMICS G130/G150
1072 List Manual (LH2), 04/2014, A5E03263479A
Fig. 3-34 2447 – E_STW1 control word infeed interconnection
- 2447 -
Function diagram
87654321
fp_2447_54_eng.vsd
DO: A_INF, B_INF, S_INF
S120/S150/G130/G150
27.06.13 V04.07.00
PROFIdrive - E_STW1 control word infeed interconnection
Signal targets for E_STW1
<1> Used in telegram 370.
<2> STW1.10 must be set to ensure that the drive object accepts the process data (PZD).
<3> Only for A_INF, S_INF
<4> Only for A_INF
<1>
STW1.0 p0840[0] = r2090.0
Signal
[Function diagram] signal target[Function diagram] internal control word
Interconnection
parameters
STW1.1 p0844[0] = r2090.1
STW1.2
STW1.3 p0852[0] = r2090.3
STW1.4 -
STW1.5 p3532= r2090.5
STW1.6 p3533= r2090.6
STW1.7 p2103[0] = r2090.7
STW1.8 -
STW1.9 -
STW1.10 p0854[0] = r2090.10
STW1.11 -
STW1.12 -
STW1.13 -
STW1.14 -
STW1.15 -
[2546.3]
-
Inverted
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
[8060]
[8920.3]
[8920.3]
-
[8920.3]
-
[8920.3]
[8920.3]
-
-
[8920.3]
-
-
-
-
-
A_INF
[8720.3]
[8720.3]
-
-
-
-
-
[8720.3]
-
-
-
-
-
-
-
B_INF <6>
[8820.3]
[8820.3]
-
[8820.3]
-
[8820.3]
-
-
[8820.3]
-
-
-
-
-
-
S_INF <5>
[8932]
-
[8932]
-
-
-
-
-
-
-
-
[8932]
[8920]
[8920]
[8920]
A_INF
[8732]
-
-
-
-
[8720]
-
-
-
-
-
[8732]
-
-
-
B_INF <6>
[8832]
[8832]
-
[8832]
-
[8820]
-
-
[8820]
-
-
-
-
-
-
S_INF <5>
= ON (close pre-charging/line contactor, pulses can be enabled)
0 = OFF1 (reduce Vdc along a ramp, suppress pulse and open pre-charging/line contactor)
Meaning
1 = No OFF2 (enable is possible)
0 = OFF2 (immediate pulse suppression and switching on inhibited)
Reserved
1 = Enable operation (pulses can be enabled)
0 = Inhibit operation (suppress pulses)
Reserved
1 = Infeed, inhibit motoring operation
1 = Infeed, inhibit regenerative operation
= Acknowledge faults
Reserved
Reserved
1 = Control via PLC
Reserved
Reserved
Reserved
Reserved
Reserved
<3>
<3>
<2>
<4>
PROFIdrive sampling time
<5> B_INF and S_INF only for S120.
<6> Only for S120 and G150
<7> Not for G130.
<7>