2 Parameters
2.2 List of parameters
SINAMICS G130/G150
520 List Manual (LH2), 04/2014, A5E03263479A
Dependency: Refer to: p2163, p2166, r2197
Description: Sets the switch-off delay time for the "speed setpoint - actual value deviation in tolerance t_off" signal/message (BO:
r2197.7).
Dependency: Refer to: p2163, p2164, r2197
Description: Sets the switch-on delay for the "speed setpoint - actual value deviation in tolerance t_on" signal/message (BO:
r2199.4).
Description: Display and connector output of the smoothed speed actual value for messages.
Dependency: Refer to: p2153
Description: Sets the torque threshold value for the messages:
"Torque setpoint < torque threshold value 1 and n_set reached" (BO: r2198.9)
"Torque setpoint < torque threshold value 1" (BO: r2198.10)
"Torque setpoint > torque threshold value 1" (BO: r2198.13)
Dependency: Refer to: p2195, r2198
p2166[0...n] Off delay n_act = n_set / t_del_off n_i=n_so
VECTOR_G Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8011
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 [ms] 10000.0 [ms] 200.0 [ms]
p2167[0...n] Switch-on delay n_act = n_set / t_on n_act=n_set
VECTOR_G Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8011
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 [ms] 10000.0 [ms] 200.0 [ms]
r2169 CO: Actual speed smoothed signals / n_act smth message
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 8010
P-Group: Messages Units group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
p2174[0...n] Torque threshold value 1 / M_thresh val 1
VECTOR_G Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8012
P-Group: Messages Units group: 7_1 Unit selection: p0505
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [Nm] 20000000.00 [Nm] 5.13 [Nm]