SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
87
2 Parameters
2.2 List of parameters
Dependency: Refer to: p0107, r0107
Note: This parameter is only significant for drive objects A_INFEED and VECTOR with a parallel circuit configuration.
Description: The power unit data set is assigned to a power unit using this parameter.
This unique component number is assigned when parameterizing the topology.
Only component numbers can be entered into this parameter that correspond to a power unit.
Dependency: Refer to: p0107, r0107
Note: For parallel circuit configurations, the parameter index is assigned to a power unit.
Description: Detects the power unit assigned to this drive and data set.
Note: While p0124 = 1, the READY LED flashes green/orange or red/orange with 2 Hz at the appropriate power unit.
For parallel circuit configurations, the parameter index is assigned to a power unit.
Description: Detection of the main components of the drive object selected via the index.
Description: Setting to activate/de-activate a power unit component.
Value: 0: De-activate component
1: Activate component
2: Component de-activate and not present
Recommend.: After inserting a component, before activating, first wait for Alarm A01317.
Dependency: Refer to: r0126
Caution: For a parallel connection, the following applies:
When deactivating individual power units using p0125, it is not permissible that the power units of the parallel
connection involved are connected. Infeed units should be disconnected from the line supply (for example, using a
contactor). Motor feeder cables should be disconnected. In addition, defective power units should be disconnected
from the DC link.
p0121[0...n] Power unit component number / PU comp_no
B_INF, VECTOR_G Can be changed: C1(4) Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: PDS, p0120 Func. diagram: -
P-Group: Data sets Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 199 0
p0124[0...n] Power unit detection via LED / PU detection LED
B_INF, VECTOR_G Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned8 Dyn. index: PDS, p0120 Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p0124[0...n] Main component detection using LED / M_comp detect LED
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p0125[0...n] Activate/de-activate power unit components / PU_comp act/deact
B_INF, VECTOR_G Can be changed: C1(4), T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: PDS, p0120 Func. diagram: -
P-Group: Data sets Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 2 1