2 Parameters
2.2 List of parameters
SINAMICS G130/G150
622 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the setpoint for the input signals in the simulation mode of the digital inputs of the Terminal Board 30 (TB30).
Dependency: The simulation of a digital input is selected using p4095.
Refer to: p4095
Note: This parameter is not saved when data is backed-up (p0971, p0977).
DI: Digital Input
Description: Sets the setpoint for the input signals in the simulation mode of the digital inputs of Terminal Module 31 (TM31).
Dependency: The simulation of a digital input is selected using p4095.
Refer to: p4095
Note: This parameter is not saved when data is backed-up (p0971, p0977).
DI: Digital Input
DI/DO: Bidirectional Digital Input/Output
Description: Sets the simulation mode for the analog inputs of the Terminal Board 30 (TB30).
p4096 TB30 digital inputs simulation mode setpoint / TB30 DI sim setpt
TB30 Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned32 Dyn. index: - Func. diagram: 9099, 9100
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X481.1) High Low -
01 DI 1 (X481.2) High Low -
02 DI 2 (X481.3) High Low -
03 DI 3 (X481.4) High Low -
p4096 TM31 digital inputs simulation mode setpoint / TM31 DI sim setp
TM31 Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned32 Dyn. index: - Func. diagram: 9549, 9550,
9552, 9560, 9562
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 0000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X520.1) High Low -
01 DI 1 (X520.2) High Low -
02 DI 2 (X520.3) High Low -
03 DI 3 (X520.4) High Low -
04 DI 4 (X530.1) High Low -
05 DI 5 (X530.2) High Low -
06 DI 6 (X530.3) High Low -
07 DI 7 (X530.4) High Low -
08 DI/DO 8 (X541.2) High Low -
09 DI/DO 9 (X541.3) High Low -
10 DI/DO 10 (X541.4) High Low -
11 DI/DO 11 (X541.5) High Low -
p4097[0...1] TB30 analog inputs simulation mode / TB30 AI sim_mode
TB30 Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: 9104
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0