SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
411
2 Parameters
2.2 List of parameters
Description: Sets the numerator damping for speed actual value filter 5.
Dependency: The speed actual value filter is activated via p1656.4 and parameterized via p1677 ... p1681.
Description: Activates data acceptance for parameter changes for the filter.
p1699 = 0:
The new filter data are immediately accepted.
p1699 = 1:
The new filter data are only accepted when this parameter is reset.
Dependency: Speed setpoint filter 1, 2 (p1414 and following)
Current setpoint filter 1 ... 4 (p1656 and following)
Current setpoint filter 5 ... 10 (function module, p5200 and following)
Refer to: p1656
Description: Sets the scaling of the dynamic current controller pre-control for the flux-generating current component Isd.
Note: The parameter is effective for permanent and separately-excited synchronous motors.
Description: Sets the scaling of the dynamic current controller pre-control for the torque/force-generating current component Isq.
p1681[0...n] Speed actual value filter 5 numerator damping / n_act_filt 5 D_n
VECTOR_G (n/M) Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 4715
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
0.000 10.000 0.700
p1699 Filter data acceptance / Filt data accept
VECTOR_G (n/M) Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p1702[0...n] Isd current controller pre-control scaling / Isd_ctr_prectrScal
VECTOR_G (n/M) Can be changed: U, T Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6714
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: ASM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.0 [%] 200.0 [%] 70.0 [%]
p1703[0...n] Isq current controller pre-control scaling / Isq_ctr_prectrScal
VECTOR_G (n/M) Can be changed: U, T Calculated: CALC_MOD_CON Access level: 4
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6714
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
0.0 [%] 200.0 [%] 70.0 [%]