2 Parameters
2.2 List of parameters
SINAMICS G130/G150
700 List Manual (LH2), 04/2014, A5E03263479A
Description: Enables the power units in the parallel circuit configuration.
Value: 0: Deactivated
1: Activated
Dependency: Refer to: r7000
Note: For motors with separate winding systems (p7003 = 1) it is not possible to inhibit an individual power unit.
p7001 is automatically reset if a power unit is de-activated via p0125 or p0895.
Description: Display and connector output for the status of the power units in a parallel connection.
Value: 0: Pulses inhibited
1: Pulses enabled
Dependency: Refer to: r7000, p7001
Description: Specifies the motor winding system when power units are connected in parallel.
Value: 0: One-winding system
1: Several separate winding systems or motors
2: Two separate offset winding systems
Dependency: Re p7003 = 2:
In order to permit separate, offset winding systems, wobbulation must first be deactivated (p1810.2 = 0). The
magnitude and direction of the offset is parameterized in p6397.
When exiting commissioning, the circulating current control is automatically deactivated (p7035 = 0), and the
compensation of the valve interlocking times is replaced by the appropriate stator resistance adaptation (p1780.7 =
1).
Refer to: p1802, p6397
Note: Re p7003 = 0:
- the motor data identification routine (p1910) determines the stator resistance and the cable resistance. The cable
resistance of an individual Motor Module is entered into p0352.
- the current symmetrizing is activated as standard after the motor data identification routine (p7035 = 1).
- individual Motor Modules can be activated and de-activated (p7001).
Re p7003 = 1, 2:
- the motor data identification routine (p1910) determines the total (overall) resistance. The cable resistance is not
measured, but instead, entered as a component of the total resistance (refer to p0352).
- all Motor Modules are activated. It is not possible to de-activate a Motor Module.
p7001[0...n] Par_circuit power units enable / PU enable
B_INF (Parallel),
VECTOR_G (Parallel)
Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: PDS, p0120 Func. diagram: -
P-Group: Modulation Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 1
r7002[0...n] CO: Par_circuit status power units / Status PU
B_INF (Parallel),
VECTOR_G (Parallel)
Can be changed: - Calculated: - Access level: 3
Data type: Integer16 Dyn. index: PDS, p0120 Func. diagram: -
P-Group: Modulation Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 -
p7003 Par_circuit winding system / Wind_sys
VECTOR_G (Parallel) Can be changed: C2(2) Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 2 0