2 Parameters
2.2 List of parameters
Re value = 6 (armature short-circuit, internal/DC braking):
The value can only be set for all motor data sets when p1231 = 3, 4.
a) For synchronous motors (p0300 = 2xx, 4xx), an internal armature short-circuit is executed.
b) For induction motors (p0300 = 1xx), a DC braking is initiated.
Re value = 7 (ENCODER (p0491)):
The fault response set in p0491 is executed if applicable.
Note:
IASC: Internal Armature Short Circuit
DCBRK: DC braking
Description: Sets the signal source to acknowledge all faults at all drive objects of the drive system.
Note: A fault acknowledgement is triggered with a 0/1 signal.
Description: Sets the first signal source to acknowledge faults.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: A fault acknowledgement is triggered with a 0/1 signal.
Description: Sets the first signal source to acknowledge faults.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: A fault acknowledgement is triggered with a 0/1 signal.
Description: Sets the second signal source to acknowledge faults.
Note: A fault acknowledgement is triggered with a 0/1 signal.
p2102 BI: Acknowledge all faults / Ackn all faults
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 2546, 8060
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p2103[0...n] BI: 1. Acknowledge faults / 1. Acknowledge
B_INF, VECTOR_G Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 2441, 2442,
2443, 2447, 2475, 2546, 9220,
9677, 9678
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p2103 BI: 1. Acknowledge faults / 1. Acknowledge
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN, ENC,
HUB, TB30, TM150,
TM31, TM54F_MA,
TM54F_SL
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: -
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p2104[0...n] BI: 2. Acknowledge faults / 2. Acknowledge
B_INF, VECTOR_G Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 2546, 8060
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0