EasyManua.ls Logo

Siemens SINAMICS G150 - SINAMICS Link Send Telegram Word PZD; Send Link Word

Siemens SINAMICS G150
1842 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS G130/G150
804 List Manual (LH2), 04/2014, A5E03263479A
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
[8] = PZD 9
[9] = PZD 10
[10] = PZD 11
[11] = PZD 12
[12] = PZD 13
[13] = PZD 14
[14] = PZD 15
[15] = PZD 16
Dependency: Refer to: p8872
Note: Value range:
0: Not used
1 ... 16: Telegram word
A pair of values p8870[index], p8872[index] may only be used once in single a device.
A change only becomes effective after POWER ON, reset, project download or p8842 = 1.
Description: Assigns a PZD to a telegram word in the SINAMICS Link send telegram.
For p8839[0] = 2 (COMM BOARD via interface 1), the following applies:
- p8871[index] assigns PZD p2051[index].
For p8839[1] = 2 (COMM BOARD via interface 2), the following applies:
- p8871[index] assigns PZD p8851[index].
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
[8] = PZD 9
[9] = PZD 10
[10] = PZD 11
[11] = PZD 12
[12] = PZD 13
[13] = PZD 14
[14] = PZD 15
[15] = PZD 16
Dependency: Refer to: p2051, p8851
p8871[0...15] SINAMICS Link send telegram word PZD / Send link word
B_INF (PROFINET
CBE20),
CU_G130_DP
(PROFINET CBE20),
CU_G130_PN
(PROFINET CBE20),
CU_G150_DP
(PROFINET CBE20),
CU_G150_PN
(PROFINET CBE20),
ENC (PROFINET
CBE20), TB30
(PROFINET CBE20),
TM150 (PROFINET
CBE20), TM31
(PROFINET CBE20),
VECTOR_G
(PROFINET CBE20)
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 16 0