2 Parameters
2.2 List of parameters
SINAMICS G130/G150
868 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the behavior for BICO interconnections to drive objects that are either not capable of operation or have been
deactivated.
BO/CO parameters are on the drive object that is either not capable of operation or has been deactivated (signal
source).
Value: 0: Inactive
1: Save interconnections
2: Save interconnections and establish the factory setting
Dependency: Refer to: p9496, p9497, p9498, p9499
Note: For p9495 = 0, the following applies:
- the number of interconnections is zero (p9497 = 0).
For p9495 not equal to 0, the following applies:
- the BI/CI parameters involved are listed in p9498[0...29] (signal sink).
- the associated BO/CO parameters are listed in p9499[0...29] (signal source).
Description: Sets the behavior when activating BICO interconnections to drive objects that are either not capable of operation or
have been deactivated.
Value: 0: Inactive
1: Restore the interconnections from the list
2: Delete the interconnections from the list
Dependency: Refer to: p9495, p9497, p9498, p9499
Note: The BI/CI parameters involved are listed in p9498[0...29] (signal sink).
The associated BO/CO parameters are listed in p9499[0...29] (signal source).
After p9496 = 1, 2 the following applies:
- p9497 = 0
- p9496 = 0
Description: Displays the number of saved BICO interconnections to drive objects that are either not capable of operation or have
been deactivated.
BO/CO parameters are on the drive object that is either not capable of operation or has been deactivated (signal
source).
Dependency: Refer to: p9495, p9496, p9498, p9499
p9495 BICO behavior for de-activated drive objects / Behav for deact DO
B_INF, CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN, ENC,
TB30, TM150, TM31,
VECTOR_G
Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 2 0
p9496 BICO behavior when activating drive objects / Behav when act DO
B_INF, CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN, ENC,
TB30, TM150, TM31,
VECTOR_G
Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 2 0
p9497 BICO interconnections to de-activated drive objects number / Interconn obj qty
B_INF, CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN, ENC,
TB30, TM150, TM31,
VECTOR_G
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 65535 0