2 Parameters
2.2 List of parameters
SINAMICS G130/G150
356 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the integral time for the I_max frequency controller.
Dependency: Refer to: p1340
Note: When p1341 = 0, the current limiting controller influencing the frequency is de-activated and only the current limiting
controller influencing the output voltage remains active (p1345, p1346).
Description: Displays the effective frequency limit.
Dependency: Refer to: p1340
Description: Displays the amount by which the converter output voltage is reduced.
Dependency: Refer to: p1340
Description: Sets the proportional gain for the I_max voltage controller.
Dependency: Refer to: p1340
Note: The controller settings are also used in the current controller of the DC braking (refer to p1232).
Description: Sets the integral time for the I_max voltage controller.
Dependency: Refer to: p1340
p1341[0...n] I_max frequency controller integral time / I_max_ctrl Tn
VECTOR_G Can be changed: U, T Calculated: CALC_MOD_CON Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6300
P-Group: U/f open-loop control Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.000 [s] 50.000 [s] 0.300 [s]
r1343 CO: I_max controller frequency output / I_max_ctrl f_outp
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6300
P-Group: U/f open-loop control Units group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
r1344 I_max controller voltage output / I_max_ctrl U_outp
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6300
P-Group: U/f open-loop control Units group: 5_1 Unit selection: p0505
Not for motor type: - Scaling: p2001 Expert list: 1
Min Max Factory setting
- [Vrms] - [Vrms] - [Vrms]
p1345[0...n] I_max voltage controller proportional gain / I_max_U_ctrl Kp
VECTOR_G Can be changed: U, T Calculated: CALC_MOD_CON Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6300, 7017
P-Group: U/f open-loop control Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.000 100000.000 0.000
p1346[0...n] I_max voltage controller integral time / I_max_U_ctrl Tn
VECTOR_G Can be changed: U, T Calculated: CALC_MOD_CON Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6300, 7017
P-Group: U/f open-loop control Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.000 [s] 50.000 [s] 0.030 [s]