2 Parameters
2.2 List of parameters
SINAMICS G130/G150
214 List Manual (LH2), 04/2014, A5E03263479A
Description: The inhibit list contains parameters that should be withdrawn from the automatic motor and closed-loop control
parameter calculation (p0340, p0578).
Value: 0: No parameter
600: Motor temperature sensor
640: Current limit
1082: Maximum speed
1460: Speed controller P gain
1462: Speed controller integral time
1470: Speed controller P gain encoderless
1472: Speed controller integral time encoderless
1520: Torque limit upper/motoring
1521: Torque limit lower/regenerative
1530: Power limit motoring
1531: Power limit regenerative
1590: Flux controller P gain
1592: Flux controller integral time
2141: Speed threshold 1
2142: Hysteresis speed 1
Note: p0570 defines the number of entries (starting at index 0) for which the inhibit should apply. p0572 can be used to
define for which drive data sets the inhibit list should apply.
If a motor data set is entered into a parameter number, then this is not overwritten as soon as only one drive data set
refers to the motor data set (p0186).
Description: Setting for activating/de-activating the inhibit list.
Depending on the setting, the parameters of the inhibit list (p0571) should be overwritten when calculating the motor
and closed-loop control parameters for the particular drive data set (DDS).
Value: 0: No
1: Yes
Note: If value = 0:
The automatic calculation (p0340, p0578) also overwrites the parameters of the inhibit list (p0571).
If value = 1:
The automatic calculation (p0340, p0578) does not overwrite the parameters of the inhibit list (p0571).
Description: Setting to inhibit the calculation of reference parameters (e.g. p2000) when automatically calculating the motor and
closed-loop control parameters (p0340, p3900).
p0571[0...49] Inhibit list motor/closed-loop control parameter calculation / Inhib list calc
VECTOR_G Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Applications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 2142 0
p0572[0...n] Activate/de-activate inhibit list / Inh_list act/deact
VECTOR_G Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Applications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p0573 Inhibit automatic reference value calculation / Inhibit calc
B_INF, VECTOR_G Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Applications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0