2 Parameters
2.2 List of parameters
SINAMICS G130/G150
768 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the communication parameters for CANopen Transmit Process Data Object 3 (TPDO 3).
Index: [0] = PDO COB-ID
[1] = PDO transmission type
[2] = Inhibit time (in 100 µs)
[3] = Reserved
[4] = Event timer (in ms)
Dependency: A valid COB-ID can only be set for the available (existing) channel.
Notice: For inhibit time and event timer, the following apply:
A value that is not a multiple integer of the CANopen sampling time is rounded-off.
Note: Corresponds to the CANopen object 1802 hex + 40 hex * x (x: Drive number 0 ... 7).
Transmission types 0, 1 ... F0, FE and FF can be set.
p8848: CANopen sampling time
PDO: Process Data Object
Description: Sets the communication parameters for CANopen Transmit Process Data Object 4 (TPDO 4).
Index: [0] = PDO COB-ID
[1] = PDO transmission type
[2] = Inhibit time (in 100 µs)
[3] = Reserved
[4] = Event timer (in ms)
Dependency: A valid COB-ID can only be set for the available (existing) channel.
Notice: For inhibit time and event timer, the following apply:
A value that is not a multiple integer of the CANopen sampling time is rounded-off.
Note: Corresponds to the CANopen object 1803 hex + 40 hex * x (x: Drive number 0 ... 7).
Transmission types 0, 1 ... F0, FE and FF can be set.
p8848: CANopen sampling time
PDO: Process Data Object
p8722[0...4] CAN Transmit PDO 3 / Transmit PDO 3
VECTOR_G (CAN) Can be changed: C1(3), T Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: 9208, 9210
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0000 hex C000 06DF hex [0] C000 06DF hex
[1] 00FE hex
[2] 0000 hex
[3] 0000 hex
[4] 0000 hex
p8723[0...4] CAN Transmit PDO 4 / Transmit PDO 4
VECTOR_G (CAN) Can be changed: C1(3), T Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: 9208, 9210
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0000 hex C000 06DF hex [0] C000 06DF hex
[1] 00FE hex
[2] 0000 hex
[3] 0000 hex
[4] 0000 hex