2 Parameters
2.2 List of parameters
Dependency: Refer to: r2197
Note: Re bit 00:
Alarm A07903 is output when the bit is set with r2197.7 = 0 (n_set <> n_act).
Re bit 01:
When the bit is set, load monitoring is only carried out in the 1st quadrant as a result of the positive characteristic
parameters (p2182 ... p2190).
Re bit 03:
When the bit is set, r2197.1 and r2197.2 are determined using separate hysteresis functions.
Re bit 15:
The bit indicates whether the automatic parameterization (p0340 = 1, p3900 > 0) for the parameters of the extended
monitoring functions was carried out.
If the bit is not set (e.g. when the configuration is activated (p0108.15)), the parameterization is automatically carried
out during booting even if r3925.0 is already 1.
Description: Sets the hysteresis speed (bandwidth) for the following signals:
"|n_act| < speed threshold value 3" (BO: r2199.0)
"n_set >= 0" (BO: r2198.5)
"n_act >= 0" (BO: r2197.3)
Dependency: Refer to: p2161, r2197, r2199
Description: Sets the signal source for the speed setpoint for the following messages:
"Speed setpoint - actual value deviation within tolerance t_off" (BO: r2197.7)
"Ramp-up/ramp-down completed" (BO: r2199.5)
"|n_set| < p2161" (BO: r2198.4)
"n_set > 0" (BO: r2198.5)
Dependency: Refer to: r2197, r2198, r2199
Bit field: Bit Signal name 1 signal 0 signal FP
00 Enable alarm A07903 Yes No 8011
01 Load monitoring only in the 1st quadrant Yes No 8013
03 Reserved -
15 Automatic parameterization carried out
(p0340 = 1, p3900 > 0)
Yes No -
p2150[0...n] Hysteresis speed 3 / n_hysteresis 3
VECTOR_G Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8010, 8011
P-Group: Messages Units group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [rpm] 300.00 [rpm] 2.00 [rpm]
p2151[0...n] CI: Speed setpoint for messages/signals / n_set for msg
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dyn. index: CDS, p0170 Func. diagram: 8011
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- - 1170[0]