SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
263
2 Parameters
2.2 List of parameters
Dependency: Refer to: p0864
Note: Re bit 00:
Bit 0 signals that the infeed is ready.
When the operating signal is transferred via binector output r0863.0 this allows several drives to start (run-up)
staggered over time when they are simultaneously powered up.
To realize this, the following connections/interconnections are required:
Drive 1: Interconnect binector input p0864 with binector output r0863.0 of the infeed
Drive 2: Interconnect binector input p0864 with binector output r0863.0 of drive 1
Drive 3: Interconnect binector input p0864 with binector output r0863.0 of drive 2 etc.
The first drive only transfers the operating signal to the next drive after it has reached its ready condition.
Re bit 01:
Bit 1 is used to control an external line contactor.
Re bit 02:
This bit only signals line supply failure for Active Infeed (A_INF) and Smart Infeed (S_INF).
Description: Sets the signal source for the operating signal of the infeed (e.g. BO: r0863.0).
Dependency: Refer to: r0863
Note: The sequence control of a servo/vector drive requires this signal.
The following applies for an infeed without DRIVE-CLiQ:
For these infeeds, the "ready" message is available via an output terminal. This signal must be connected to a digital
input. The drives supplied from this infeed must use this signal as ready signal (BI: p0864 = digital input).
Description: Sets the main contactor holding time after OFF1
Dependency: Refer to: p0869
Note: After withdrawing the OFF1 enable (source of p0840), the main contactor is opened after the main contactor holding
time has elapsed.
For p0869 = 1 (keep main contactor closed for STO), after withdrawing STO, the switch-on inhibit must be
acknowledged via the source of p0840 = 0 (OFF1) – and before the main contactor holding time expires, should go
back to 1, otherwise the main contactor will open.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Closed-loop control operation Yes No 2610,
8710,
8810,
8910
01 Energize contactor Yes No 2610,
2634,
7990,
8734,
8834,
8934
02 Infeed line supply failure Yes No -
p0864 BI: Infeed operation / INF operation
VECTOR_G Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 2610, 8710,
8910
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p0867 Power unit main contactor holding time after OFF1 / PU t_MC after OFF1
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 [ms] 500.0 [ms] 50.0 [ms]