2 Parameters
2.2 List of parameters
SINAMICS G130/G150
650 List Manual (LH2), 04/2014, A5E03263479A
If the deviation is less than this limit, the PPR is not corrected. If it is higher than this limit, fault F3x131 is triggered.
If fault F3x131 is re-parameterized to alarm (A) or no message (N), the encoder pulses which have not been
corrected are added to the accumulator (p4688). The accumulator can be de-activated using p0437.7.
Dependency: Refer to: p0437, p4681, p4688
Note: This monitoring is activated by setting p0437.2 = 1 (position actual value correction).
For a set value = -1001, the negated value of p4681 is effective.
The negative limit describes the pulses lost due to a covered glass panel in the incremental encoder.
Description: Sets the positive tolerance window in encoder pulses for limit 2 for the zero mark monitoring.
If the zero mark deviation is higher than the tolerance set in p4681 and p4682 and fault F3x131 is re-parameterized
to alarm (A) or no message (N), the accumulator p4688 is compared with this parameter and, if applicable, alarm
A3x422 is output for 5 seconds.
Dependency: Refer to: p0437, p4681, p4682, p4688
Note: Zero mark monitoring is activated by setting p0437.2 = 1 (position actual value correction).
Description: Sets the negative tolerance window in encoder pulses for limit 2 for the zero mark monitoring.
If the zero mark deviation is higher than the tolerance set in p4681 and p4682 and fault F3x131 is re-parameterized
to alarm (A) or no message (N), the accumulator p4688 is compared with this parameter and, if applicable, alarm
A3x422 is output for 5 seconds.
Dependency: Refer to: p0437, p4683, p4688
Note: Zero mark monitoring is activated by setting p0437.2 = 1 (position actual value correction).
For a set value = -100001, the negated value of p4683 is effective.
Description: Sets the number of current controller clock cycles for mean value generation of the speed actual value.
Note: Value = 0, 1: No mean value generation.
Higher values also mean higher dead times for the speed actual value.
p4683[0...n] Zero mark monitoring tolerance window alarm threshold positive / ZM tol A_thr pos
ENC, VECTOR_G Can be changed: C2(4) Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: EDS, p0140 Func. diagram: -
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 100000 0
p4684[0...n] Zero mark monitoring tolerance window alarm threshold negative / ZM tol A_thr neg
ENC, VECTOR_G Can be changed: C2(4) Calculated: - Access level: 3
Data type: Integer32 Dyn. index: EDS, p0140 Func. diagram: -
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-100001 0 -100001
p4685[0...n] Speed actual value mean value generation / n_act mean val
ENC, VECTOR_G Can be changed: C2(4) Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: EDS, p0140 Func. diagram: -
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 20 0