SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
127
2 Parameters
2.2 List of parameters
Description: Sets the current for the 1st phase of the two-stage technique for pole position identification routine.
The current of the 2nd phase is set in p0329.
The two-stage technique is selected with p1980 = 4.
Dependency: Refer to: p0329, p1980, p1982, r1984, r1985, r1987, p1990
Notice: When the motor code (p0301) is changed, it is possible that p0325 is not pre-assigned.
p0325 can be pre-assigned using p0340 = 3.
Note: The value is automatically pre-assigned for the following events:
- For p0325 = 0 and automatic calculation of the closed-loop control parameters (p0340 = 1, 2, 3).
- for quick commissioning (p3900 = 1, 2, 3).
Description: Sets the optimum load angle for synchronous motors with reluctance torque (e.g. 1FE motors).
SERVO: The load angle is measured at 1.5 x rated motor current.
VECTOR: The load angle is measured at the rated motor current.
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note: This parameter has no significance for induction motors.
For synchronous motors without reluctance torque, a angle of 90 degrees must be set.
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
Description: Sets the reluctance torque constant for synchronous motors with reluctance torque (e.g. 1FE ... motors).
This parameter has no significance for induction motors.
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note: For synchronous motors without reluctance torque, the value 0 must be set.
p0325[0...n] Motor pole position identification current 1st phase / Mot PolID I 1st ph
VECTOR_G Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: ASM, REL, FEM Scaling: - Expert list: 1
Min Max Factory setting
0.000 [Arms] 10000.000 [Arms] 0.000 [Arms]
p0327[0...n] Optimum motor load angle / Mot phi_load opt
VECTOR_G Can be changed: C2(3), U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 5722, 6721
P-Group: Motor Units group: - Unit selection: -
Not for motor type: ASM, FEM Scaling: - Expert list: 1
Min Max Factory setting
0.0 [°] 135.0 [°] 90.0 [°]
p0328[0...n] Motor reluctance torque constant / Mot kT_reluctance
VECTOR_G Can be changed: C2(3), U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: ASM, REL, FEM Scaling: - Expert list: 1
Min Max Factory setting
-1000.00 [mH] 1000.00 [mH] 0.00 [mH]