SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
101
2 Parameters
2.2 List of parameters
Note: The parameter is used to identify when the drive is being commissioned for the first time.
The power unit commissioning can only be exited (p0201 = r0200), if the actual and acknowledged code numbers are
identical (p0010 = 2).
For parallel circuit configurations, the parameter index is assigned to a power unit.
Description: Sets the actual code number from r0200 to acknowledge the power unit being used.
When commissioned for the first time, the code number is automatically transferred from r0200 into p0201.
Notice: When p0201 = 10000, the rated power unit data is reloaded and dependent parameters are set (e.g. p0205, p0210,
p0230, p0857, p1800). p0201 is then automatically assigned the value of r0200 if the code number of the power unit
could be read. A warm start must be performed after this procedure (automatically if necessary).
Note: The parameter is used to identify when the drive is being commissioned for the first time.
The power unit commissioning can only be exited (p0201 = r0200), if the actual and acknowledged code numbers are
identical (p0010 = 2). However, if the comparator in p9906 or p9908 is at 2 (low) or 3 (minimum), the power unit
commissioning is automatically set to p0201 = r0200 upon exiting.
When the code number is changed, the connection voltage (p0210) is checked and, if necessary, adjusted.
For parallel circuit configurations, the parameter index is assigned to a power unit.
Description: Displays the type of power unit found.
Value: 2: MICROMASTER 440
3: MICROMASTER 411
4: MICROMASTER 410
5: MICROMASTER 436
6: MICROMASTER 440 PX
7: MICROMASTER 430
100: SINAMICS S
101: SINAMICS S (value)
102: SINAMICS S (combi)
103: SINAMICS S120M (distributed)
112: PM220 (SINAMICS G120)
113: PM230 (SINAMICS G120)
114: PM240 (SINAMICS G120)
115: PM250 (SINAMICS G120 / S120)
116: PM260 (SINAMICS G120)
118: SINAMICS G120 Px
120: PM340 (SINAMICS S120)
126: SINAMICS ET200PRO
130: PM250D (SINAMICS G120D)
133: SINAMICS G120C
135: SINAMICS PMV40
136: SINAMICS PMV60
137: SINAMICS PMV80
138: SINAMICS G110M
150: SINAMICS G
151: PM330 (SINAMICS G120)
200: SINAMICS GM
p0201[0...n] Power unit code number / PU code no
VECTOR_G Can be changed: C2(2) Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: PDS, p0120 Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 65535 0
r0203[0...n] Actual power unit type / PU actual type
B_INF, VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: Integer16 Dyn. index: PDS, p0120 Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
2 400 -