2 Parameters
2.2 List of parameters
SINAMICS G130/G150
440 List Manual (LH2), 04/2014, A5E03263479A
Note: The load-dependent adaptation of the leakage inductance of the current actual value correction is defined using
p0391 ... p0393.
Description: Sets the damping factor for the actual value correction.
The factor multiplies the T0/Tsig ratio in the feedback branch of the LR element.
Description: Displays phase correction currents as well as the drive converter phase currents
Index: [0] = Harmonics phase U
[1] = Harmonics phase V
[2] = Harmonics phase W
[3] = Measured value phase U
[4] = Measured value phase V
[5] = Measured value phase W
Description: Displays the phase correction voltages and and the drive converter phase voltages
Index: [0] = Harmonics phase U
[1] = Harmonics phase V
[2] = Harmonics phase W
[3] = Measured value phase U
[4] = Measured value phase V
[5] = Measured value phase W
Description: Sets the motor data identification and speed controller optimization.
p1900 = 0:
Function inhibited.
p1846[0...n] Actual value correction damping factor / ActV_corr D_factor
VECTOR_G Can be changed: U, T Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Modulation Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 10.00 1.00
r1848[0...5] Actual value correction phase currents / ActVal_corr I_ph
VECTOR_G Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Modulation Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r1849[0...5] Actual value correction phase voltages / ActVal_corr U_ph
VECTOR_G Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Modulation Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
p1900 Motor data identification and rotating measurement / MotID and rot meas
VECTOR_G Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Motor identification Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 2 2