EasyManua.ls Logo

Siemens SINAMICS G150 - TB30 Invert Digital Outputs; TB30 DO Inv; TM31 Invert Digital Outputs; TM31 DO Inv; CO: TB30 Analog Inputs Actual Input Voltage; TB30 AI U_Inp Act

Siemens SINAMICS G150
1842 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS G130/G150
606 List Manual (LH2), 04/2014, A5E03263479A
Description: Setting to invert the signals at the digital outputs of the Terminal Board 30 (TB30).
Note: DO: Digital Output
Description: Setting to invert the signals at the digital outputs of Terminal Module 31 (TM31).
Note: DO: Digital Output
DI/DO: Bidirectional Digital Input/Output
Description: Displays the actual input voltage at the analog inputs for Terminal Board 30 (TB30).
Note:
For p4056[x] = 3 (unipolar current input monitored (+4 mA ... +20 mA)) the following applies:
A current less than 4 mA is not displayed in r4052[x] - but instead r4052[x] = 4 mA is output.
Index: [0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Note: AI: Analog Input
p4048 TB30 invert digital outputs / TB30 DO inv
TB30 Can be changed: U, T Calculated: - Access level: 1
Data type: Unsigned32 Dyn. index: - Func. diagram: 9102
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 DO 0 (X481.5) Inverted Not inverted -
01 DO 1 (X481.6) Inverted Not inverted -
02 DO 2 (X481.7) Inverted Not inverted -
03 DO 3 (X481.8) Inverted Not inverted -
p4048 TM31 invert digital outputs / TM31 DO inv
TM31 Can be changed: U, T Calculated: - Access level: 1
Data type: Unsigned32 Dyn. index: - Func. diagram: 9556, 9560,
9562
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 0000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 DO 0 (X542.1 - 3) Inverted Not inverted -
01 DO 1 (X542.4 - 6) Inverted Not inverted -
08 DI/DO 8 (X541.2) Inverted Not inverted -
09 DI/DO 9 (X541.3) Inverted Not inverted -
10 DI/DO 10 (X541.4) Inverted Not inverted -
11 DI/DO 11 (X541.5) Inverted Not inverted -
r4052[0...1] CO: TB30 analog inputs actual input voltage / TB30 AI U_inp act
TB30 Can be changed: - Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9104
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- [V] - [V] - [V]