2 Parameters
2.2 List of parameters
Description: Displays the actual input voltage in V when set as voltage input.
Displays the actual input current in mA when set as current input and with the load resistor switched in.
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Dependency: The type of analog input AI x (voltage or current input) is set using p4056.
Refer to: r4056, p4056
Note: AI: Analog Input
Description: Sets the smoothing time constant of the 1st-order low pass filter for the analog inputs of the Terminal Board 30
(TB30).
Index: [0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Note: AI: Analog Input
Description: Sets the smoothing time constant of the 1st-order low pass filter for the analog inputs of Terminal Module 31 (TM31).
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Note: AI: Analog Input
Description: Displays the currently referred input value of the analog inputs of Terminal Board 30 (TB30).
When interconnected, the signals are referred to the reference quantities p200x and p205x.
Index: [0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Note: AI: Analog Input
r4052[0...1] CO: TM31 analog inputs current input voltage/current / TM31 AI U/I_inp
TM31 Can be changed: - Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9566, 9568
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
p4053[0...1] TB30 analog inputs smoothing time constant / TB30 AI T_smooth
TB30 Can be changed: U, T Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9104
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 [ms] 1000.0 [ms] 0.0 [ms]
p4053[0...1] TM31 analog inputs smoothing time constant / TM31 AI T_smooth
TM31 Can be changed: U, T Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9566, 9568
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 [ms] 1000.0 [ms] 0.0 [ms]
r4055[0...1] CO: TB30 analog inputs actual value in percent / TB30 AI value in %
TB30 Can be changed: - Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9099, 9104
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]