2 Parameters
2.2 List of parameters
SINAMICS G130/G150
588 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the ramp-up/ramp-down time of the ramp-up/ramp-down function generator to automatically record the friction
characteristic.
The drive is accelerated from standstill (setpoint = 0) up to the maximum speed/velocity (p1082) in this time.
Dependency: Refer to: p3845
Description: Sets the warm-up time.
For an automatic trace (record) to start, the highest selected speed (p3829) is approached and this time is held. After
this, the measurement is started with the highest speed.
Dependency: Refer to: p3829, p3845
Description: Sets the number of Braking Modules connected in parallel in a DC link.
Note: The parameter can only be written to if the infeed is in the commissioning mode (p0010 = 2).
Description: Signal to energize terminal X21.1 "inhibit/acknowledgement" on the Braking Module.
This binector output is used as signal source to interconnect to a digital output.
For "booksize" formats the digital output must be connected to terminal X21.1 and for "chassis" formats the digital
output must be connected to terminal X21.3 of the particular Braking Module.
p3846[0...n] Friction characteristic record ramp-up/ramp-down time / Frict rec t_RU/RD
VECTOR_G (n/M) Can be changed: T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 7010
P-Group: Functions Units group: - Unit selection: -
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
0.000 [s] 999999.000 [s] 10.000 [s]
p3847[0...n] Friction characteristic record warm-up time / Frict rec t_warm
VECTOR_G (n/M) Can be changed: T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 7010
P-Group: Functions Units group: - Unit selection: -
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
0.000 [s] 3600.000 [s] 0.000 [s]
p3860 Number of Braking Modules connected in parallel / BM qty par_cct
B_INF (Brk Mod ext) Can be changed: C2(2) Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: 9951
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 8 1
r3861.0...7 BO: Braking Module inhibit/acknowledgement / BM inhib/ackn
B_INF (Brk Mod ext) Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: 9951
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Inhibit/acknowledge Braking Module 1 High Low -
01 Inhibit/acknowledge Braking Module 2 High Low -
02 Inhibit/acknowledge Braking Module 3 High Low -
03 Inhibit/acknowledge Braking Module 4 High Low -
04 Inhibit/acknowledge Braking Module 5 High Low -
05 Inhibit/acknowledge Braking Module 6 High Low -
06 Inhibit/acknowledge Braking Module 7 High Low -
07 Inhibit/acknowledge Braking Module 8 High Low -